Model PC991 devices are modular devices that have been designed to measure and control different types of processes variables and all modules can be configured seperately. Complying international standards, reliability and user friendly usage features are the design principles of these devices. So that, they are ergonomic devices that can be used easily in many different industrial sectors.
For the detailed information about device, [Device Cataloque] ve [User's Guide] links can be used.
- 2 Item 4 Digit 1 Item 3 Digit Display
- 1 Item 21 LED’li Bar Indicator
- 6 Item LED Indicator
- 1 Item Transmitter Supply Output (24Vdc)
- 1 Item Universal Sensor Input (TC, RT, mA, mV, V )
- 1 Item Auxiliary Analog Input(0/4-20mA)
- 1 Item Potentiometer Input (100-1500W)
- 3 Item Digital Input (15V)
- 1 Item RS485 Communication Unit
- 2 Item Analog Output (0/4-20mA, 0/2-10V)
- 4 Item Relay or Logic Output (24V)
- 100-240Vac Universal or 24Vac/dc Supply
- Isolation between Input/Output Modules
- 800 Step, 100 Program Step Controls
- Programing Ability of Relays in Different Steps
- 7 Different Power-Cut Action
- Proportional Valve Control with position feedback
- Proportional Valve Control without feedback(Floating Control)
- PID Heating/Cooling
- Auto-Tuning (Automatic settings of PID parameters)
- Automatic/Manual/Program Operating Modes
- Bumpless Transfer Ability
- Sensor Error Detection
- Remote Set Point (Determining Set Point Remotely)
- 8 Item Optional Set Point
- Ramp Function
- Retransmission (For Process and Set Vaues)
- 18 Different Relay Functions
- ON/OFF, P, PI, PD, PID Controls
- Linear and Time Proportioning Control Output
- 100ms Sampling and Control Cycle
- Standard MODBUS RTU Communication Protocol
|
|
|
|
|


|
| TECHNICAL SPECIFICATIONS |
| Supply Voltage |
100-240Vac/dc: +%10- %15 |
24Vac/dc: +%10- %20 |
| Power Consumption |
6W, 10VA |
| Universal Sensor Input(S1) |
Thermocouple :B,E,J,K,L,N,R,S,T,U |
| Two Wire Transmitter: 4-20 mA |
| Resistance Thermometer: PT100 |
| Current: 0/4mA |
| Voltage: 0-50mV, 0/2-10V |
| Auxiliary Analog Input(S2) |
0/4-20mA |
| Potentiometer Input(S3) |
100-1500 Ω |
| Transmitter Supply(TX) |
24Vdc (Isc=30mA) |
| Analog Input Impedance |
Thermocouple, mV:10M Ω |
| Current: 10 Ω |
| Voltage: 1M Ω |
| Analog Output(O1,O2) |
Current: 0/4-20mA
(RL≤500 Ω) |
Voltage: 0/2V-10V
(RL ≥ 1MΩ ) |
| Relay Outputs(R1,R2,R3,R4) |
Contact: 250Vac 3A |
Logic Output : 24Vdc 20mA |
| Contact Lifetime |
Without Load: 10.000.000 switching, with 250V 3A resistive load: 100.000 switching |
| Memory |
100 year, 100.000 renewals |
| Accuracy |
+/- % 0.2 |
| Sampling Period |
100ms |
| Environment Temperature |
Operation: -10...+55° C |
Storage: -20...+65° C |
| Protection |
Front Panel: IP54, Trunk:IP20 |
| Dimensions |
Width: 96mm, Height: 96mm, Depth: 110mm |
| Panel Cut-Out Dimensions |
92+/-0,5mm x 92+/-0,5 mm |
| Weight |
430gr |
| |
|