UST200 Model devices are used to convert analog signals that are created in any environment to standart analog signals isolated from input. These devices have two universal analog input and two analog output.
These devices are based with microcontrollers and can be configured easily by using SBA100 USB/UART Converter.
All inputs and outputs are isolated.
For the detailed information about device,[Device Catalog] ve [Users Guide] links can be used.
|
|
|
|
|


SENSOR TYPE |
STANDARD |
Temperature Range |
(° C) |
(° F ) |
Type-B Thermocouple |
IEC584-1 |
60, 1820 |
140, 3308 |
Type-E Thermocouple |
IEC584-1 |
-200, 840 |
-328, 1544 |
Type-J Thermocouple |
IEC584-1 |
-200, 1120 |
-328, 1562 |
Type-K Thermocouple |
IEC584-1 |
-200, 1360 |
-328, 2480 |
Type-L Thermocouple |
DIN43710 |
-200, 900 |
-328, 1652 |
Type-N Thermocouple |
IEC584-1 |
-200, 1300 |
-328, 2372 |
Type-R Thermocouple |
IEC584-1 |
-40, 1760 |
104, 3200 |
Type-S Thermocouple |
IEC584-1 |
-40, 1760 |
104, 3200 |
Type-T Thermocouple |
IEC584-1 |
-200, 400 |
-328, 752 |
Type-U Thermocouple |
DIN43710 |
-200, 600 |
-328, 1112 |
PT-100 |
IEC751 |
-200, 840 |
-328, 1544 |
|
| TECHNICAL SPECIFICATIONS |
| Supply Voltage |
100-240Vac/dc: +%10- %15 |
24Vac/dc: +%10- %20 |
| Power Consumption |
2W, 3VA |
| Analog Inputs(I1,I2) |
Thermocouple :B,E,J,K,L,N,R,S,T,U |
| Resistance Thermometer: PT100 |
| Current: 0/4-20mA |
| Voltage: 0-50mV |
| Analog Input Impedances |
Thermocouple, mV:10MΩ |
| Current: 10 Ω |
| Analog Outputs(O1,O2) |
Current: 0/4-20mA
(RL≤500Ω) |
Voltage: 0/2V-10V
(RL ≥ 1MΩ ) |
| Contact Lifetime |
Without load : 10.000.000 switching, with 250V 3A resistive load: 100.000 switching |
| Memory |
100 year, 100.000 renewals |
| Accuracy |
+/- % 0.2 |
| Sampling Period |
400ms |
| Environment Temperature |
Operation: -10...+55° C |
Storage: -20...+65° C |
| Protection |
Gövde:IP20 |
| Dimensions |
Width: 25mm, Height: 91mm, Depth: 113mm |
| Weight |
134gr |
| |
|