| Supply Voltage |
100-240Vac/dc: +%10- %15 |
24Vac/dc: +%10- %20 |
| Power Consumption |
4W, 6VA |
| Universal Sensor Input(S1) |
Thermocouple :B,E,J,K,L,N,R,S,T,U |
| Two Wire Transmitter: 4-20 mA |
| Resistance Thermometer: PT100 |
| Current: 0/4mA |
| Voltage: 0-50mV, 0/2-10V |
| Transmitter Supply(TX) |
24Vdc (Isc=30mA) |
| Analog Input Impedance |
Thermocouple, mV:10MΩ |
| Current: 10 Ω |
| Voltage: 1M Ω |
| Analog Output(O1) |
Current: 0/4-20mA
(RL≤500Ω) |
Voltage: 0/2V-10V
(RL ≥ 1MΩ ) |
| Relay Outputs(R1,R2) |
Contact: 250Vac 3A |
Logic Output : 24Vdc 20mA |
| Contact Lifetime |
Without Load: 10.000.000 switching, with 250V 3A resistive load: 100.000 switching |
| Memory |
100 year, 100.000 renewals |
| Accuracy |
+/- % 0.2 |
| Sampling Period |
100ms |
| Environment Temperature |
Operation: -10...+55° C |
Storage: -20...+65° C |
| Protection |
Front Panel: IP54, Trunk:IP20 |
| Dimensions |
Width: 48mm, Height: 48mm, Depth: 108mm |
| Panel Cut-Out Dimensions |
45+/-0,5mm x 45+/-0,5 mm |
| Weight |
154gr |